JLS-10KY Switchgear
JLS-10KY Switchgear
+
  • JLS-10KY Switchgear
  • JLS-10KY Switchgear
Zhengzhou KBT Transformer Instrument Co., Ltd.

JLS-10KY Switchgear

The product consists of JLS-10 combined transformer, ZW43-12/630 column vacuum circuit breaker and BXK control box. It shares the installation base with the transformer and high-voltage switch.

Categories:

Switchgear

1. Overview

The product consists of JLS-10 combined transformer, ZW43-12/630 column vacuum circuit breaker and BXK control box. It shares the installation base with the transformer and high-voltage switch. The structure is simple and reliable, which reduces the on-site installation workload of the product and maintains the convenience of independent maintenance and expansion of the transformer and switch. Through the user-provided negative control terminal with prepaid function or the optional company's GPRS-type negative control terminal, the remote prepaid function is realized and the power consumption prepaid management is an ideal product for reforming the power consumption system, realizing the commercialization of electricity, and effectively controlling electricity.

2. Model and meaning

 

3. Structure introduction

This type of combined transformer adopts a fully enclosed structure of the user's external epoxy resin. It is made of three fully insulated single-phase voltage transformers, "Y"-shaped wiring A, B, and phase C, respectively, and is suitable for power metering in power lines of 10kV and below. To prevent power theft, the secondary terminal sealing plate can be directly poured into a conspicuous position on the surface of the casting body, and a lead seal can be added to effectively prevent power theft.

4. Technical parameters

1. Rated insulation level: 12/42/75kV 

2. Product Standard: GB/T 20840.4-2015 "Combination Transformer"

3. Dirt level: Level IV

4. Load power factor: COSΦ=0.8 (hysteresis)

5. Ambient temperature: -25℃ ~ +45℃

6. Altitude: £1000m

7. Installation location: outdoor

8. Rated secondary current: 5A, 1A

9. Instrument security coefficient: 10

10. Rated primary current: 5 ~ 600A (double conversion ratio)

11. Rated capacity: PT: 0.2 grade, 15VA; CT: 0.2S grade, 10VA;

12. Rated short-term thermal current (Ith): 100In/1s

13. Rated dynamic stable current (Idyn): 2.5Ith 

14. Rated voltage ratio: 10/Ö3/0.1/Ö3 (kV) or 10/0.1, 0.22k V power winding can be used for short-term loads such as circuit breaker closing and opening, energy storage, etc.

15. Switch parameter table

project

parameter

Rated current

630A

Rated short circuit breaking current 

20

Rated peak withstand current (peak)

50

Rated short circuit closing current (peak value)

50

Rated short-term withstand current 4s  

20

Rated short circuit current break times

30

Mechanical life

10,000 times

Contact distance mm   

9±1

Contact closing bounce time ms  

£2

Three-phase split and closing different periods ms  

£2

Closed time ms  

25-45

Opening time ms  

23-45

Secondary loop operating voltage

AC220

The distance between the centers of the phases mm   

280±1.5

Housing material

Stainless steel shell

 

5. Appearance and installation dimensions

Three components

Two components

Notes:

If the user has special requirements, he or she can negotiate with our factory to confirm.

Key words:

High voltage metering box

Get A Quote

Leave your contact information and get a free product quote

Related Products

Zhengzhou KBT Transformer Instrument Co., Ltd. is a specialized production enterprise mainly based on power transformers, which integrates product development,production, sales, service and technology consulting.

JLS-6、10E 10kV high voltage metering box


This product is an outdoor structure composed of two parts: combined transformer and meter box.The product is five column type.The voltage transformer adopts V/V connection method and is connected in parallel between AB and CB to form a three-phase measuring device.

JLS-10AY 10kV high voltage metering box


This product is an outdoor structure composed of two parts: combined transformer and meter box. The product is six column type,which is connected by three voltage transformers Y/Y and three current transformers.

JLS-10H 10kV high voltage metering box


JLSZV-10 integral casting high voltage dry type combined transformer (integral casting high voltage metering box) is improved on the basis of similar products. It is suitable for rated frequency of 50Hz and rated voltage 10kV and below outdoor AC system for active and reactive energy measurement, which is the replacement of the old oil metering box products.

JLS-10HY 10kV high voltage metering box


JLSZV-10 integral casting high voltage dry type combined transformer (integral casting high voltage metering box) is improved on the basis of similar products. It is suitable for rated frequency of 50Hz and rated voltage 10kV and below outdoor AC system for active and reactive energy measurement, which is the replacement of the old oil metering box products.