JDZ10-10C3 voltage transformer
This type of voltage transformer is cast using epoxy resin and is a pillar-type fully enclosed structure. It is suitable for use in power systems with a rated frequency of 50Hz and a rated voltage of 6kV and 10kV for voltage, power measurement and relay protection. When the transformer is excitated at a rated voltage, it can withstand an external short circuit of 1 second without damage, and is suitable for use in various high-voltage switch cabinets.
Categories:
Voltage transformer
1. Overview
This type of voltage transformer is cast using epoxy resin and is a pillar-type fully enclosed structure. It is suitable for use in power systems with a rated frequency of 50Hz and a rated voltage of 6kV and 10kV for voltage, power measurement and relay protection. When the transformer is excitated at a rated voltage, it can withstand an external short circuit of 1 second without damage, and is suitable for use in various high-voltage switch cabinets.
2. Model and meaning

3. Structure introduction
This type of transformer is fully enclosed. The iron core is made of high-quality cold-rolled silicon steel sheets and is strictly heat treated. The iron core is poured with epoxy resin together with the primary and secondary windings. The product has good foul-resistant and moisture resistance.
4. Technical data
1.GB/T 20840.1-2010 "Transformers Part 1: General Technical Requirements"
2.GB/T 20840.3-2013 "Supplementary Technical Requirements for Transformers Part 3 Electromagnetic Voltage Transformers"
3. Insulation level: 12/42/75kV
4. The product surface creepage ratio meets the level II filth level;
5. Load power factor: cosФ=0.8 (hysteresis);
6. Frequency: 50Hz or 60Hz.
7. Ambient atmospheric temperature: -5~+40℃ average temperature 30℃;
8. Relative temperature ≤85% (20℃);
9. Altitude ≤1000m;
10. Other technical parameters are shown in the table below
|
model |
Rated voltage ratio (kV) |
Accurate combination |
Rated output (VA) |
Extreme output (VA) |
|
JDZ10-10C3 |
10/0.1 |
0.2/0.5 |
15VA |
300VA |
5. Wiring diagram

6. Appearance and installation dimension drawings

7. Ordering instructions
1. Voltage ratio
2. Rated secondary load
3. Accurate series
8. Things to note
1. After wiring, check whether all wiring is correct, especially short connections cannot be formed between the voltage secondary outlets a-b.
2. The base ground terminal must be grounded on the site, and the transformer secondary outlet is reliably connected to ground according to regulations. Please note that the double-variable voltage secondary terminals a and b cannot be grounded at the same time.
3. The primary line installation A must be the incoming side and B is the outgoing side.
4. Pay attention to protecting the terminal board and umbrella group during handling and hoisting. It is strictly forbidden to directly lift or transport the transformer terminal board and umbrella group.
Key words:
Voltage transformer
Previous
Previous
Get A Quote
Leave your contact information and get a free product quote
Related Products
Zhengzhou KBT Transformer Instrument Co., Ltd. is a specialized production enterprise mainly based on power transformers, which integrates product development,production, sales, service and technology consulting.
This series of current transformers features an epoxy‑resin‑cast, fully enclosed insulation design. They are suitable for use in power systems with a rated frequency of 50 Hz or 60 Hz for electrical energy metering. These transformers eliminate oil contamination and fire hazards, reduce maintenance requirements, and meet the demands of oil‑free operation.
The LZZB current transformer is an epoxy‑resin‑cast, fully enclosed device, primarily intended for power systems with a rated frequency of 50 Hz or 60 Hz and a rated voltage of 35 kV or lower. Its core function is to provide high‑accuracy current signals for energy metering, current measurement, and relay protection. This model features excellent dynamic and thermal stability, high accuracy, and a large capacity.
The LZZBJ9-10A current transformer is primarily designed for indoor power systems with a rated frequency of 50 Hz and a rated voltage of 10 kV or less (with a maximum operating voltage of 12 kV). Its core functions are to accurately measure current and electrical energy in the circuit and to provide reliable signals to relay protection devices. This model is widely used in indoor switchgear—such as center‑mounted switchgear and cubicle switchgear—as well as in complete high‑ and low‑voltage equipment sets.
The LZZB1-35W current transformer is an epoxy‑resin‑cast, fully enclosed device, primarily intended for power systems with a rated frequency of 50 Hz or 60 Hz and a rated voltage of 35 kV or lower. Its core function is to provide high‑accuracy current signals for energy metering, current measurement, and relay protection. This model is specifically designed to interface with equipment such as the ZW‑type 35 kV vacuum circuit breaker, offering superior dynamic and thermal stability, high accuracy, and large capacity.