LZZW-10 Current transformer
This type of current transformer is an outdoor epoxy resin cast insulated fully enclosed structure. It is suitable for use in outdoor power systems with a rated voltage of 10kV and below and a rated frequency of 50Hz or 60Hz for current, electrical energy measurement and relay protection. This type of transformer can replace the LB type oil-immersed transformer, which can avoid oil pollution and fire hazards, reduce maintenance work, and adapt to the requirements of oil-free.
Categories:
Current transformer
Overview
This type of current transformer is an outdoor epoxy resin cast insulated fully enclosed structure. It is suitable for use in outdoor power systems with a rated voltage of 10kV and below and a rated frequency of 50Hz or 60Hz for current, electrical energy measurement and relay protection. This type of transformer can replace the LB type oil-immersed transformer, which can avoid oil pollution and fire hazards, reduce maintenance work, and adapt to the requirements of oil-free.
Model and meaning

Structure introduction
This type of transformer uses external epoxy resin as the left insulating material, and has the characteristics of arc resistance, ultraviolet resistance, and aging resistance. The iron core adopts high-quality, high-magnetic material and is annealed. The primary and secondary windings and the iron core are poured into epoxy resin, which has excellent insulation properties. The primary outlet is on the top of the casting body. The outgoing marks are P1 and P2, the measurement stage winding outgoing marks are 1S1, 1S2 and 1S3, the monitoring stage winding outgoing marks are 2S1, 2S2 and 2S3, and the protection stage winding outgoing marks are 3S1, 3S2 and 3S3 (the secondary outlet signs do not have 1S3, 2S3 and 3S3 in a single-change ratio). The transformer is polarity reduction, and there is a junction box in the secondary outlet part, and the lead wire is drawn out from the bottom of the casting body. There are 4 mounting holes on the base for installation.
Technical data
Insulation level: 12/42/75 kV;
Product Standard: GB/T 20840.1-2010 GB/T 20840.2-2014
Load power factor: COSø=0.8 (hysteresis);
Surface creepage distance: meets the requirements of Level III filth level;
Ambient temperature: minimum temperature -5℃, maximum temperature 40℃;
Instrument security coefficient FS=5, 10;
Accurate limit coefficient ALF=10, 15;
Rated secondary current: 5A (or 2A, 1A)
Other technical parameters are shown in the table below:
|
Rated primary current |
Level combination |
Rated load (VA) |
Instrument security factor |
Accurate limit coefficient |
Rated short-term thermal current kA, effective value |
Rated dynamic stable current kA, peak value |
|
50 |
0.2S/0.5/10P10 |
15/15/15VA |
10 |
10 |
5 |
12.5 |
|
75 |
7.5 |
18.5 |
||||
|
100 |
10 |
25 |
||||
|
150 |
15 |
37.5 |
||||
|
200 |
20 |
50 |
||||
|
300 |
25 |
64 |
||||
|
400 |
31.5 |
80.3 |
||||
|
500 |
31.5 |
80.3 |
||||
|
600 |
31.5 |
80.3 |
Appearance and installation dimensions

Ordering instructions
1. Current ratio
2. Accurate series
3. Rated secondary load
Things to note
1. After wiring, check whether all wiring is correct, especially the current secondary outlet XS1 and XS2 or XS3 cannot form an open circuit.
2. The base ground terminal must be grounded on the site, and the transformer secondary outlet wire is reliably connected to ground according to regulations. Please note that the double-variable current secondary terminals S2 and S3 cannot be grounded at the same time.
3. The primary line installation must be P1 as the incoming side and P2 as the outgoing side.
4. Pay attention to protecting the terminal boards and umbrella groups during transportation and hoisting. It is strictly forbidden to directly lift or transport the transformer terminal boards and umbrella groups.
Key words:
Current transformer
Get A Quote
Leave your contact information and get a free product quote
Related Products
Zhengzhou KBT Transformer Instrument Co., Ltd. is a specialized production enterprise mainly based on power transformers, which integrates product development,production, sales, service and technology consulting.
This series of current transformers features an epoxy‑resin‑cast, fully enclosed insulation design. They are suitable for use in power systems with a rated frequency of 50 Hz or 60 Hz for electrical energy metering. These transformers eliminate oil contamination and fire hazards, reduce maintenance requirements, and meet the demands of oil‑free operation.
The LZZB current transformer is an epoxy‑resin‑cast, fully enclosed device, primarily intended for power systems with a rated frequency of 50 Hz or 60 Hz and a rated voltage of 35 kV or lower. Its core function is to provide high‑accuracy current signals for energy metering, current measurement, and relay protection. This model features excellent dynamic and thermal stability, high accuracy, and a large capacity.
The LZZBJ9-10A current transformer is primarily designed for indoor power systems with a rated frequency of 50 Hz and a rated voltage of 10 kV or less (with a maximum operating voltage of 12 kV). Its core functions are to accurately measure current and electrical energy in the circuit and to provide reliable signals to relay protection devices. This model is widely used in indoor switchgear—such as center‑mounted switchgear and cubicle switchgear—as well as in complete high‑ and low‑voltage equipment sets.
The LZZB1-35W current transformer is an epoxy‑resin‑cast, fully enclosed device, primarily intended for power systems with a rated frequency of 50 Hz or 60 Hz and a rated voltage of 35 kV or lower. Its core function is to provide high‑accuracy current signals for energy metering, current measurement, and relay protection. This model is specifically designed to interface with equipment such as the ZW‑type 35 kV vacuum circuit breaker, offering superior dynamic and thermal stability, high accuracy, and large capacity.